SciELO - Scientific Electronic Library Online

 
vol.31 suppl.2Entropy and coefficient of variation (CV) as tools for assessing power qualityA Study of incentives to increase the use of DG in Colombia based on a System Dynamics modeling author indexsubject indexarticles search
Home Pagealphabetic serial listing  

Services on Demand

Journal

Article

Indicators

Related links

  • On index processCited by Google
  • Have no similar articlesSimilars in SciELO
  • On index processSimilars in Google

Share


Ingeniería e Investigación

Print version ISSN 0120-5609

Abstract

ARANGUREN, D. et al. Operational analysis of electric field mills as lightning warning systems in Colombia. Ing. Investig. [online]. 2011, vol.31, suppl.2, pp.51-57. ISSN 0120-5609.

Electrostatic field measurements taken in Bogotá, Colombia, during thunderstorms in November (the rainy season due to inter-tropical confluence zone over central Colombia) were used to study the performance of an isolated electric field sensor and analyse its most important operational characteristics. The distances from each flash to the studied sensor were obtained by using the Colombian lightning location system. The ΔE cf distance ratio led to defining a charge model which could be used as a reference for calibrating other electrostatic field sensors to be used as lightning warning systems.

Keywords : thunderstorm; electric field mill; operational analysis; lightning warning system.

        · abstract in Spanish     · text in English     · English ( pdf )

 

Creative Commons License All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License