SciELO - Scientific Electronic Library Online

 
vol.35 suppl.1Electrical performance of distribution insulators with chlorella vulgaris growth on its surfaceFault location in power distribution systems considering a dynamic load model índice de autoresíndice de assuntospesquisa de artigos
Home Pagelista alfabética de periódicos  

Serviços Personalizados

Journal

Artigo

Indicadores

Links relacionados

  • Em processo de indexaçãoCitado por Google
  • Não possue artigos similaresSimilares em SciELO
  • Em processo de indexaçãoSimilares em Google

Compartilhar


Ingeniería e Investigación

versão impressa ISSN 0120-5609

Resumo

ARANGUREN, D et al. Lightning effects on distribution transformers and reliability of power distribution systems in Colombia. Ing. Investig. [online]. 2015, vol.35, suppl.1, pp.28-33. ISSN 0120-5609.  https://doi.org/10.15446/ing.investig.v35n1Sup.54069.

Failure rates of rural power systems are statistically studied based on lightning parameters and a two-state weather model (normal and adverse). Lightning information is matched with geographical coordinates of 251,024 power transformers in a vast area in Central Colombia. An important portion of transformers present failure rates 45 times higher than normal, and very large overhead lines, representing a high portion of the total system, present very high failure rates over 75 times higher than in normal weather conditions.

Palavras-chave : Power reliability; lightning; weather reliability model; tropical zone.

        · resumo em Espanhol     · texto em Inglês     · Inglês ( pdf )