Resumen
RIOS, Carlos Alberto; GRANADA E., Mauricio y GALLEGO, Ramón Alfonso. Optimal location and sizing of capacitors in electrical distribution systems with harmonic pollution using simulated annealing. rev.ing. [online]. 2006, n.24, pp.52-61. ISSN 0121-4993.
The Simulated Annealing Algorithm is used to solve the problem of optimal placement and sizing of fixed capacitor banks in distribution networks in the presence of harmonic electrical signals. In the mathematical model, the objective function includes the cost of power and energy losses at each harmonic frequency, and the inverting cost of capacitor banks. Constrains include voltage limits, power quality limits, number, size and locations of capacitors banks. A harmonic load fl ow was implemented as analysis tool.
Palabras clave : Harmonics; capacitor banks; non linear loads; harmonic power flow; combinatorial optimization; Simulated Annealing.