SciELO - Scientific Electronic Library Online

 
vol.20 issue2Mechanical characterization of aluminum-silicon coating deposited by CVD-FBR on austenitic stainless steel AISI 316 and vapor oxidation author indexsubject indexarticles search
Home Pagealphabetic serial listing  

Services on Demand

Journal

Article

Indicators

Related links

  • On index processCited by Google
  • Have no similar articlesSimilars in SciELO
  • On index processSimilars in Google

Share


Ingeniería y competitividad

Print version ISSN 0123-3033

Abstract

PIEDRAHITA-VELASQUEZ, Carlos A.; CIRO-VELASQUEZ, Héctor J.  and  ARANGO-TOBON, Julio C.. Improvement of transient performance and power efficiency of a variable-speed compressor refrigeration system using anti-windup control methodology. Ing. compet. [online]. 2018, vol.20, n.2, pp.9-18. ISSN 0123-3033.  https://doi.org/10.25100/iyc.v20i2.6752.

This paper presents a control methodology to improve the transient performance and power efficiency of a refrigeration system that uses a variable-speed compressor. The control objective is to maintain the compartment temperature at the desired setpoint, despite varying heat load conditions or disturbances. A model of the refrigeration system was obtained. The variables of interest were the compartment temperature, the evaporator superheat temperature, and the speed of the variable-speed compressor. By using simulations and real tests of the refrigeration system, it was found that a conventional implementation of a closed-loop controller causes a phenomenon known as windup, which leads to variable-speed compressor saturation and diminishes the transient performance of the refrigeration system and increases power consumption. Additionally, the evaporator superheat temperature was not significantly affected by the speed of the variable compressor, so the only option for improving the coefficient of performance of the refrigeration system was reducing the power consumption of the variable-speed compressor. An anti-windup topology for the closed-loop controller was proposed to prevent variable-speed compressor saturation. Simulations and tests of the refrigeration system showed an important improvement of the transient performance and power efficiency of the refrigeration system.

Keywords : refrigeration system; variable-speed compressor; anti-windup topology; closed-loop control system.