vol.83 issue197Assessing the loss-of-insulation life of power transformers by estimating their historical loads and ambient temperature profiles using ANNs and Monte Carlo simulationsStatistical performance of control charts with variable parameters for autocorrelated processes author indexsubject indexarticles search
Home Pagealphabetic serial listing  

Services on Demand

Journal

Article

Indicators

Related links

  • On index processCited by Google
  • Have no similar articlesSimilars in SciELO
  • On index processSimilars in Google

Share


DYNA

Print version ISSN 0012-7353

Dyna rev.fac.nac.minas vol.83 no.197 Medellín May/June 2016

https://doi.org/10.15446/dyna.v83n197.48653 

DOI: http://dx.doi.org/10.15446/dyna.v83n197.48653

Thermal assessment of ecological tiles in physical models of poultry houses

Evaluación térmica de tejas ecologicas en modelos físicos de galpones avicolas

 

Flavio Alves Damasceno a, Leonardo Schiassi a, Tadayuki Yanagi Junior a, Jairo Alexander Osorio-Saraz b & Jofran Luiz-de Oliveira c

 

a Departamento de Ingeniería, Universidad Federal de Lavras, Lavras, Brasil. flavio.damasceno@deg.ufla.br, leoschiassi@yahoo.com.br, yanagi@deg.ufla.br
b Facultad de Ciencias Agrarias, Universidad Nacional de Colombia, Medellín, Colombia. aosorio@unal.edu.co
c Departamento de Ingeniería Agrícola, Universidad Federal de Mato Grosso, Cuiabá, Brasil. joframluiz@gmail.com

 

Received: January 27th, 2015 Received in revised form: August 11th, 2015. Accepted: February 25th, 2016.

 

This work is licensed under a Creative Commons Attribution-NonCommercial-NoDerivatives 4.0 International License.


Abstract
In countries with tropical climates, such as Brazil, the high summer temperatures associated with high relative humidities are a stress factor in animal production. Excessive heat within a poultry facility causes a reduction in feed intake and production, and increased bird mortality. With the knowledge that about 75% of the radiant heat load within a facility comes from the roof, it is necessary to study alternatives that can minimize this radiation. Thus, the objective of the present work is to analyze the thermal environment inside physical broiler housing models constructed on a reduced scale (1:10), where the thermal comfort was evaluated by the black globe humidity index (BGHI) and radiant heat load (RHL). Five models built with different roofing materials were evaluated. Based on the results, it can be concluded that roofs constructed with the channel clay roofing tile (TB30), natural fiber tiles with their external side painted white (TFVP15) and tiles made of recycled long-life packaging (TLV15), provide better thermal environments within the models.

Keywords: reduced models, thermal environment, alternative materials, thermal capacity.

Resumen
En países con climas tropicales, como Brasil, las altas temperaturas asociadas con altas humedades relativas en el verano contribuyen como un factor de estrés en la producción animal. El calor excesivo dentro de una instalación avícola causa una reducción en el consumo de alimento y en la producción, y aumento en la mortalidad de las aves. Conociendo que el 75% de la carga de calor radiante dentro de una instalación viene desde el techo, es necesario estudiar alternativas que pueden minimizar esta radiación. El objetivo del presente trabajo fue analizar el ambiente térmico dentro de los modelos físicos de instalaciones de pollos de engorde construidos a escala reducida (1:10), donde el confort térmico se evaluó por el índice de humedad y de globo negro (BGHI) y la carga de calor radiante (RHL). Cinco modelos construidos fueron evaluados con diferentes materiales para techos. Basados en los resultados, se puede concluir que los techos construidos con tejas de cerámica (TB30), placas de fibra natural pintadas de blanco con en el lado externo (TFVP15) y placas de fabricadas con envases larga vida reciclado (TLV15), proporcionan los mejores ambientes térmicos.

Palabras clave: modelos a escala, ambiente térmico, materiales alternativos, capacidad térmica.


 

1. Introduction

The use of ecological tiles is an uncommon practice despite the potential to use industrial and urban waste when manufacturing them.

For many years, in the construction and agricultural industries, roofs have been built with traditional materials such as fiber-cement, ceramics and aluminum. Current environmental concerns have forced architects and engineers to review the materials used in civil construction, and they now favor the use of renewable and less polluting energy sources [1].

The roof most commonly used in Brazilian poultry facilities are fiber-cement tiles, which are simple to install, maintain and clean (in comparison to traditional ceramic tiles) in addition to costing less. This is mainly because the support structure is lighter and requires less labor [2,3]. Another advantage is that these tiles may also be combined with other methods, such as a reflective paint and water sprinkling on the external surface in order to decrease the temperature inside the facility [4].

In Brazil, a country with a tropical climate and high summer temperatures that receives intense solar radiation, the materials to construct roofs should provide good thermal insulation for the internal environment of the installations so they are less influenced by the outside climate [5].

According to some researchers [6], of the thermal radiation received from various parts of the installation surrounding an animal in the shade, 28% of the radiant heat load comes from the sky, 21% from the roofing, 18% from the unshaded area and 33% from the shaded area.

The current trend of studies on agricultural projects in South American countries that occupy a prominent place on the world stage, such as Brazil, Colombia and Argentina, is focused on the technical and economic evaluation of technologies seeking to increase efficiency since the global economy requires the poultry industry to be more productive and at the same time more profitable.

In tropical and subtropical countries, the importance of studying new roofing materials and especially ecological materials lies in the wealth of natural resources that these countries possess and the high incidence of direct solar radiation, especially in the summer. According to [7], incident solar radiation generates thermal discomfort, which is mostly related to the roofing material and the type of thermal cooling used, in humans and in animals housed inside production installations.

This discomfort increases the risk of work-related accidents in addition to exposing the body to various conditions such as hyperthermia, dizziness and others. Animal discomfort causes a reduction in growth performance and increased mortality rate [8].

In this context, the construction of ecological roofs has begun to use plant cellulose fiber, paper and recycled long-life packaging. These types of roofs have some advantages including: being eco-friendly, having good thermal and acoustic insulation, good mechanical strength, impermeability, and are socially inclusive and generate employment and income.

As these new eco-friendly materials are being used in the construction of roofing tiles, the agro-industrial sector requires technical information on the damping capacity of the radiant heat load provided by these materials.

Due to limited economic resources and to save time performing studies seeking to evaluate roofing materials, it is common to use physical broiler house models built on a reduced scale [9-14]. According to [12], the use of these physical models is based on the theory of similarity, which intends to establish relationships that allow for real predictions to be made based on observations of smaller models.

Therefore, the objective of this study was to evaluate the efficiency of ecological tiles to reduce the radiant heat load. It seeks to look for improvements in the thermal environment of facilities for broilers.

 

2. Material and methods

2.1. Construction and field deployment of the reduced models

In order to undertake this experiment, five models at a reduced scale of 1:10 were constructed, based on the methodology used by [9,11-14] for east-west oriented poultry houses, They had different types of roofing as indicated in Table 1, were constructed according to the cross-section schematic of the models (Fig. 1) and arranged according to the overview of the experimental area (Fig. 2).

The physical models were deployed in the experimental area at the Construction and Ambience Sector of the Engineering Department, Federal University of Lavras, located in southern Minas Gerais - Brazil (21°14' S latitude and 45°00' W longitude, located 918 m above sea level). The local climate, according to the Köppen climate classification, is Cwa: a humid temperate with a dry winter.

In order to construct small-scale models, real dimensions of a commercial poultry house for production of broiler chickens were used as the basis, with a standard that is adopted worldwide (12.0 m wide, 120.0 m long, ceiling height of 3.5 m and distance between roof trusses of 5.0 m).

In the construction, 1 cm thick plywood panels were used that were reinforced by a 3 x 3 cm wood structure. After construction, the models were 1.2 m wide, 1.5 m long and had a distance between roof trusses of 0.5 m. There were three sections of 5 m that represented the distance between pillars. All constructed roofs had 2.0 meter overhangs. The central sector of physical models was used to set the measuring sensors of environmental variables.

The east and west sides of the buildings were completely closed with plywood. The side had a height of 0.5 cm, corresponding to the real sheds' existing 5 cm low walls. The buildings' floors were elevated from the soil by 0.4 m, making the air flow at floor height approximately the same, with respect to a real shed [11,12]. All reduced physical models had the ridges of the roofs oriented in the east-west direction since they are located in the southern hemisphere.

2.2. Instrumentation and measurements

The dry bulb temperature (Tdb), black globe temperature (Tbg), relative humidity (RH) and air velocity (V) variables were measured in the constructed physical reduced scale models and in the external environment over a period of seven non-consecutive typical summer days, with a clear sky, between 12 and 16 h. These conditions present severe thermal discomfort conditions, at 15-minute intervals. After this process, the respective values of BGHI and RHL were calculated for the measurement times.

Inside the reduced scale physical models, sensors were installed at the height corresponding to the geometric center of the birds, i.e., 3 cm from the floor (30 cm in the actual buildings). In the external environment, climate data was collected in a weather shelter that was installed in the experimental area, except for Tbg and V, whose sensors were allocated at the height corresponding to the geometric center of the birds.

2.2.1. Dry bulb, wet bulb and black globe temperatures

The thermal environment was assessed by the Tdb, Tbg and RH, in which these three variables were measured by means of sensors / recorders (Hobo®, mod. U12-013, accurate to ±3 %). In each reduced model, one sensor / Tdb, Tbg and RH recorder were installed. These sensors were housed inside a perforated protective container in order to prevent damage to equipment. Readings were compared to a sensor outside of the protection in order to verify any interference that the protective container had on equipment measurements. In the case of Tbg, only the recorder was housed in the protective container, since the temperature sensor was inserted into a plastic sphere measuring 3.6 cm in diameter and painted matte black. The recorder-sensor assembly was calibrated against a standard made of copper, with a 15 cm diameter and 0.5 mm thickness, painted black.

2.2.2. Air velocity

The air velocity was measured using a digital propeller anemometer (Kestrel® mod. 4000, accurate to ± 3%). Measurements were obtained in the vicinity of each black globe, on the same days and at the same times.

2.2.3. Climatic variables of the external environment

External climate data was collected using a weather shelter installed in the experimental area. In this shelter, sensors were installed to measure air temperature and humidity. Thus, Tdb and RH data could be developed using measurements at 15-minute intervals, indicating the average, maximum and minimum. A black globe thermometer was installed in the external environment to quantify the BGHI and RHL of the external environment.

2.3. Determination of the thermal indices

From the Tdb data, dew point temperature (Tdp), Tbg and V measured at the predetermined times, the respective BGHI and RHL values for each measurement time were calculated according to eq. 1 and 2, respectively.

where:

Tbg: black globe temperature, K;
Tdp: dew point temperature, K.

where:

s: Stefan-Boltzmann constant (s = 5.67 x 10-8 W m-2 K-4);
Tm: mean radiant temperature, calculated by eq. 3.

Classification of materials used in the roofs or their designs was performed by effectiveness ( e), which may be defined in relation to the BGHI [18, 3, 28, 11] by eq. 4.

2.4. Experimental design and statistical analysis

We used a randomized block design (RBD), in which the treatments were arranged in a split-plot design, with seven repetitions (measurement days) The plots were attributed to the constructed reduced scale models with the different roofs, and subplots with the measurement times. The mean BGHI and RHL for the treatments were compared with the Skott-Knott test at a 5% probability. The Sisvar 4.6 software [14] was used for statistical analysis.

 

3. Results and discussion

Results from the analysis of variance for the response variables BGHI and RHL (W. m-2) are presented in Table 2. It was verified that for both the BGHI and RHL there was a significant difference (p<0.05) for the treatments and measurement times. However, no significant difference was observed for the interaction of treatments x measurement time (p>0.05).

Regarding the BGHI, the coefficients of variation for the plots and subplots were 2.64% and 1.33%, respectively; and for the RHL they were 3.37% and 2.65%. This demonstrated little variability of the observed models in relation to the means.

For both the RHL and BGHI (Table 3), the treatments that resulted in the best thermal comfort conditions inside the reduced physical models were TB30, TFVP15 and TLV15, which are statistically equal (Skott-Knott test, p<0.05). The other treatments presented poorer results (Skott-Knott test, p>0.05).

The results obtained for the BGHI and RHL are in accordance with those observed by [16] and [17], where TB30 presented the best efficiency when compared with the other materials due to its reflective capacity and porosity. It is therefore statistically equal to TFVP15 and TLV15 and different in relation to TFVN15 and TAL15.

When considering tiles constructed of natural plant fiber sealed with bitumen, a better efficiency was observed when they were painted with two coats of hydrated lime on the external surface. This effect was similar to that encountered when using white paint on fiber-cement tiles, as observed by [16,18,19], where it was shown that the use of reflective paint on the tiles resulted in improved thermal performance.

Mean BGHI values observed in treatments TB30 and TFVP15 were in agreement with those found by [20], from 69.0 to 77.0, where adult birds have the highest productivity and best performance parameters.

The RHL values for all treatments were lower than those found in [19], 498.3 (W. m-2), and [21], 502.7 W m-2 (average of the times) for sheds with clay tiles. Reduction of the BGHI by the roofs varied from 7.09 to 5.60% for the best (TB30) and worst (TAL15) treatment, respectively. For the RHL, the change was 20.24% to 18.68% for the best (TB30) and worst (TFVN15) treatment. The RHL reduction results are within the range suggested by several authors, which is from 20 to 40% [22-25].

Fig. 3 shows the average internal and external behaviors of the BGHI and RHL, depending on the time of day for the tested treatments, and the lower and upper limits of thermal comfort for the BGHI. The lower and upper limits of BGHI that prevented the broilers from suffering stress had values of 69.1 and 77.5, respectively, and were in accordance with the recommendations reported by other studies [21,27,28].

The classification of effectivities ( e) of the roofs is presented in Table 4. Behavior was observed similar to that found for [11,28]. These results complement the information in the literature related to the classification of roofs made of different types of materials, especially those obtained by [3,11].

Through analysis of the BGHI, RHL and e, it was verified that the roofs TB30, TFVP15 and TLV15 provided the best thermal comfort conditions inside the physical reduced-scale models. This is due to the increased thermal resistance of the roof, an effect of the thickness of the material and the light color, as shown by [11].

 

4. Conclusions

The roofs constructed with tiles made of ceramic, plant fiber, painted bitumen and recycled long-life packaging provided the best thermal comfort conditions inside the physical broiler housing models built on a reduced scale (1:10). Statistically equal results were obtained. Average reduction of the black globe humidity index (BGHI) and radiant heat load (RHL) were 6.88% and 19.91%, respectively.

 

Acknowledgements

The authors thank the CAPES, CNPq and FAPEMIG for their financial support of the project.

 

References

[1] Silva, R.B., Nääs, I.A., Moura, D.J. e Silveira, N.A., Insalubridade do trabalhador na produção animal: Uma questão de educação e informação. Segurança e Trabalho, Brasil, 2006.         [ Links ]

[2] Conceição, M.N., Alves, S.P., Telatin Júnior, A., Silva, I.J.O., Piedade, S.M.S., Savastano-Júnior, H. e Tonoli, G., Desempenho de telhas de escória de alto forno e fibras vegetais em protótipos de galpões. Revista Brasileira de Engenharia Agrícola e Ambiental, 12(5), pp. 536-539, 2008. DOI: 10.1590/S1415-43662008000500015        [ Links ]

[3] Moraes, S.R.P., Tinôco, I.F.F., Cecon, P.R. e Baêta, F.C., Conforto térmico em galpões avícolas, sob coberturas de cimento-amianto e suas diferentes associações. Revista Brasileira de Engenharia Agrícola e Ambiental, 3(1), pp. 89-92, 1999. DOI: 10.1590/1807-1929/agriambi.v3n1p89-92        [ Links ]

[4] Abreu, P.G. e Abreu, V.M.N., Análise termográfica da temperatura superficial de telhas. Revista Brasileira de Engenharia Agrícola e Ambiental, 15(11), pp. 1193-1198, 2011. DOI: 10.1590/S1415-43662011001100013        [ Links ]

[5] Abreu, P.G., Abreu, V.M.N. e Dalla-Costa, O.A., Avaliação de coberturas de cabanas de maternidade em sistema intensivo de suínos criados ao ar livre (Siscal), no verão. Revista Brasileira de Zootecnia, 30(1), pp. 1728-1734, 2001. DOI: 10.1590/S1516-35982001000700010        [ Links ]

[6] Bond, T.E., Morrison, S.R.and Givens, R.L., Influence of surrounding on radiant heat load of animals. Transactions of the ASAE., 12(2), pp. 246-248, 1969. DOI: 10.13031/2013.38809        [ Links ]

[7] Oliveira, L.M.F., Efeitos climáticos no conforto térmico animal e humano. Tese de MeSc, Departamento de Engenharia Agrícola, Universidade Federal de Lavras, Lavras, Brasil, 2004.         [ Links ]

[8] Damasceno, F.A., Yanagi-Junior, T., Lima, R.R., Gomes, R.C.C. e Moraes, S.R.P., Avaliação do bem-estar de frangos de corte em dois galpões comerciais climatizados. Ciência Agrotecnica, 34(2), pp. 1031-1038, 2010. DOI: 10.1590/S1413-70542010000400033.         [ Links ]

[9] Murphy, G.C.E., Similitude in engineering. New York: Ronal Press, 1950.         [ Links ]

[10] Pattie, D.R. and Milne, W.R., Ventilation air-flow patterns by use of models. Transactions of the ASAE, 9(5), pp. 646-9, 1966. DOI: 10.13031/2013.40062        [ Links ]

[11] Santos, P.A., Yanagi-Junior, T., Teixeira, V.H. e Ferreira, L., Ambiente térmico no interior de modelos de galpões avícolas em escala reduzida com ventilação natural e artificial dos telhados. Engenharia Agrícola, 25(3), pp. 575-584, 2005. DOI: 10.1590/S0100-69162005000300002        [ Links ]

[12] Jentzsch, R., Baêta, F.C., Tinôco, I.F.F., Damasceno, F.A., Cecon, P.R. e Tibiriçá, A.C.G., Predição de parâmetros térmicos ambientais no interior de modelos físicos de galpões avícolas construídos em escalas reduzidas. Interciencia, 36(1), pp. 1-5, 2011.         [ Links ]

[13] Jentzsch, R., Baêta, F.C., Tinôco, I.F.F., Damasceno, F.A. e Osório, J.A., Parâmetros arquitetônico-ambientais para construção e testes em modelos reduzidos, representativos de galpões avícolas, com base em similitude. Engenharia na Agricultura, 21 (1), pp. 19-30, 2013. DOI: 10.13083/1414-3984.v21n01a02        [ Links ]

[14] Carvalho, H.G., Materiais de cobertura e suas associações a forros e materiais isolantes no ambiente térmico de protótipos abertos e fechados com vistas a produção de frangos de corte em clima quente. Dissertação de Dr., Departamento de Engenharia Agrícola, Universidade Federal de Viçosa, Viçosa, Brasil, 2013.         [ Links ]

[15] Ferreira, D.F., Sistema de análise estatística para dados balanceados - SISVAR. Lavras: UFLA/DEX, 2000.         [ Links ]

[16] Sevegnani, K.B., Ghelfi-Filho, H. e Silva, I.J.O., Comparação de vários materiais de cobertura através de índices de conforto térmico. Scientia Agrícola, 51(1), pp.1-7, 1994. DOI: 10.1590/S0103-90161994000100001        [ Links ]

[17] Jácome, I.M.T.D., Furtado, D.A., Leal, A.F., Silva, J.H.V. e Moura, J.F.P., Avaliação de índices de conforto térmico de instalações para poedeiras no nordeste do Brasil. Revista Brasileira de Engenharia Agrícola e Ambiental, 11(5), pp. 527-531, 2007. DOI: 10.1590/S1415-43662007000500013        [ Links ]

[18] Kelly, C.F. and Bond, T.E., Effectiveness of artificial shade materials. Agriculture Engineering, St. Joseph, 39(12), pp.758-764, 1958.         [ Links ]

[19] Rosa, Y.B.C.J., Influência de três materiais de cobertura no índice de conforto térmico em condições de verão, para Viçosa. Tese de MSc., Departamento de Engenharia Agrícola, Universidade Federal de Viçosa, Viçosa, Brasil, 1984.         [ Links ]

[20] Medeiros, C.M., Baêta, F.C., Oliveira, R.F.M., Tinôco, I.F.F., Albino, L.F.T. e Cecon, P.R., Efeitos da temperatura, umidade relativa e velocidade do ar em frangos de corte. Engenharia na Agricultura, 13(4), pp. 277-286, 2005.         [ Links ]

[21] Furtado, D.A., Azevedo, P.V. e Tinoco, I.F.F., Análise do conforto térmico em galpões avícolas com diferentes sistemas de acondicionamento. Revista Brasileira de Engenharia Agrícola e Ambiental, 7(3), pp. 559-564, 2003. DOI: 10.1590/S1415-43662003000300025        [ Links ]

[22] Santos, A.C., Baêta, F.C., Cecon, P.R. e Cardoso, R.M. Análise de diferentes bezerreiros individuais móveis, para região de Viçosa. Engenharia na Agricultura, 2(7), pp. 1-8, 1993.         [ Links ]

[23] Turco, S.H.N., Baêta, F.C., Costa, P.M.A., Cardoso, R.M. e Cecon, P.R., Modificações das condições ambientais de verão em maternidades de suínos. Engenharia na Agricultura, 3(11), pp. 1-12, 1994.         [ Links ]

[24] Abreu, P.G., Baêta, F.C., Soares, A.R., Abreu, U.M.N. e Maciel, N.F., Utilização de piso aquecido eletricamente na criação de aves. Engenharia na Agricultura, 4(12), pp. 1-19, 1995.         [ Links ]

[25] Baêta, F.C., Souza, C.F., Ambiência em Edificações Rurais: Conforto Animal. 2ª Ed. Viçosa-MG: Editora UFV, 2010.         [ Links ]

[26] Teixeira, V.H., Estudo dos índices de conforto em duas instalações de frango de corte para as regiões de Viçosa e Visconde do Rio Branco, MG. Tese de MSc. Departamento de Engenharia Agrícola, Universidade Federal de Viçosa, Viçosa, Brasil, 1983.         [ Links ]

[27] Tinôco, I.F.F., Resfriamento adiabático (evaporativo) na produção de frangos de corte. Tese de MSc, Departamento de Engenharia Agrícola, Universidade Federal de Viçosa, Viçosa, Brasil, 1988.         [ Links ]

[28] Ferreira-Júnior, L.G., Yanagi-Junior, T., Damasceno, F.A., Silva, E. e Silva, G.C.A., Ambiente térmico no interior de modelos físicos de galpões avícolas equipados com câmaras de ventilação natural e artificial. Engenharia na Agricultura, 17(1), pp. 166-178, 2009. DOI: 10.13083/1414-3984.v17n03a01        [ Links ]

 

F.A. Damasceno, is adjunct professor at the Universidade Federal de Lavras (UFLA), Brazil. PhD in Environment Control from the Federal University of Viçosa (UFV), Brazil with training in Biosystems and Agricultural Engineering from the University of Kentucky, as a visiting researcher. MSc. of Environment Control from the UFLA in 2008, Sp. Management Specialist and Environmental Management in Agribusiness from UFLA in 2008, and BSc. in Agricultural Engineering from UFLA in 2006. He has publication scientific papers in conferences and national and international journals. ORCID: 0000-0002-4181-0611

L. Schiassi, is professor at the Federal University of Lavras (UFLA), Brazil, in the Engineering Department. Researcher in COAMBI - Research Group Constructions and Ambience in Biosystems - DEG / UFLA. PhD in Rural and Ambience Constructions, Master of Systems Engineering. He has experience in Agricultural Engineering with an emphasis on Rural Construction Engineering, working mainly in the areas of construction and ambience, Building Materials, Bioclimatology, Noise, Animal Welfare and Human, Evaluation and Building Systems Modeling and Ambience, Analysis Fuzzy Systems and Neural Networks. ORCID: 0000-0002-8284-7496

T. Yanagi-Junior, has a BSc degree in Agricultural Engineering in 1992 and is a Professor at the Federal University of Lavras, Brazil. His MSc. degree is in Agricultural Engineering from Federal University of Lavras in 1995 and PhD in Agricultural Engineering from the Federal University of Viçosa, Brazil, in 2002. He has experience in Agricultural Engineering, and focuses on Agricultural Constructions and Environment. ORCID: 0000-0001-9653-205X

J.A. Osorio-Saraz, has a BSc. degree in Agricultural Engineering in 1998, a Post Graduate Degree in Environmental Legislation in 2001 and a MSc. in Materials Engineering in 2006, all from the Universidad Nacional de Colombia, Medellín, Colombia). In 2011 he gained a Dr. degree in Rural Constructions from the Federal University of Viçosa, Minas Gerais state, Brazil. Since 2003 he has worked as a professor at the Universidad Nacional de Colombia, teaching and advising in the following areas: Design of Livestock Housing, Materials Technology for Livestock Housing, air quality and animal welfare, thermal comfort for animals, use of the CFD tool to predict air motion patterns in agro industry facilities. He is member of AMBIAGRO (Center for Research in Agro-Industrial Ambience and Engineering Systems) at the Department of Agricultural Engineering, Federal University of Viçosa and of the research group in agricultural engineering (A1 in Colciencias Colombia) at the UNAL. He is currently the Dean of the Faculty of Agricultural Sciences at UNAL Medellin, and has been since 2012. ORCID: 0000-0002-4358-3600

J. Luiz-de Oliveira, has a BSc. degree in Agricultural Engineering in 2010 from the Federal University of Viçosa, Minas Gerais state, Brazil. Since 2010 he has worked as a Professor at the Universidade Federal de Mato Grosso (UFMT), Brazil, teaching and advising in the following areas: Thermal Comfort in Livestock Facilities and Materials technologies for Thermal Control Improvement. He is member of AMBIAGRO (Center for Research in Agro-Industrial Ambience and Engineering Systems) at the Department of Agricultural Engineering, Federal University of Viçosa and ECOAGRI (Engineering and Sustainability in Agriculture) at UFMT. ORCID: 0000-0002-9093-3773