Generation of electric pomer and air conditioning by cogeneration: a proposal for energy saving

Producción de energía eléctrico y aire acondicionado por cogeneración: Una propuesta de ahorro de energía

Produção de energia elétrica e ar condicionado por cogeração: Uma proposta de economia de energia

Iván Vera-Romero* 

* M. Sc. Universidad de la Ciénega del Estado de Michoacán de Ocampo (Michoacán, México). ivera@ucienegam.edu.mx. ORCID: 00000003-1771-6630.


Abstract

This paper presents the results of a case study carried out in a warehouse, and, in particular, the technical data obtained from field visits and a proposal for energy saving. The proposal entails incorporating a cogeneration system based on a motor generator (400 kWe ISO) to produce electrical energy, and an absorption cooling system (75 TR) that uses residual heat to generate air-conditioning. The absorption chiller consumed 54% less energy than the conventional air-conditioning system. Moreover, the produced energy can supply the plant's total consumption, in addition to offering an excess of 57,312 kWh per month, which was reflected in the analysis of energy for sale to users with a high domestic consumption rate (DAC, for its Spanish acronym). The proposal's total investment is USD 1,091,258, with a net monthly savings of USD 30,901, and an investment payback period of 2.9 years, which indicates the viability of this project according to its energy characteristics, notwithstanding that it is for a service provider company.

Keywords: absorption cooling; cogeneration; cost-benefit analysis; energetic consulting; energy savings

Resumen

Este trabajo es resultado de un estudio de caso realizado en una bodega. Se muestran en él los datos técnicos obtenidos a partir de la visita de campo y una propuesta energética. La propuesta consta de la incorporación de un sistema de cogeneración basado en un motogenerador (400 kWe ISO) para producir energía eléctrica y de un sistema de refrigeración por absorción (75 TR) que aproveche el calor residual para generar aire acondicionado. Se observó que el chiller de absorción consume 54 % menos energía que el sistema convencional de aire acondicionado empleado. Por otra parte, la energía producida abastece el total del consumo de la planta, además de ofrecer un excedente de 57,312 kWh por mes, el cual se tomó en el análisis como energía de venta a usuarios con tarifa doméstica de alto consumo (DAC). La inversión total de la propuesta es de 1 091 258 USD, con un ahorro neto mensual de 30 901 USD y un tiempo de recuperación de la inversión de 2.9 años, lo que indica la viabilidad de este proyecto de acuerdo con sus características energéticas, a pesar de tratarse de una empresa que brinda servicios.

Palabras clave: ahorro de energía; análisis costo-beneficio; cogeneración; consultoría energética; refrigeración por absorción

Resumo

Este trabalho é resultado de um estudo de caso realizado em um porão. Mostram-se neste estudo os dados técnicos obtidos a partir da visita de campo e uma proposta energética. A proposta consta da incorporação de um sistema de cogeração baseado em um motogerador (400 kWe ISO) para produzir energia elétrica e de um sistema de refrigeração por absorção (75 TR) que aproveite o calor residual para gerar ar condicionado. Observou-se que o chiller de absorção consome 54% menos energia que o sistema convencional de ar condicionado empregado. Por outra parte, a energia produzida abastece o total do consumo da usina, além de oferecer um excedente de 57,312 kWh por mês, o qual se tomou na análise como energia de venda a usuários com tarifa doméstica de alto consumo (DAC). A inversão total da proposta é de 1 091 258 USD, com uma economia líquida mensal de 30 901 USD e um tempo de recuperação da inversão de 2.9 anos, o que indica a viabilidade deste projeto de acordo com suas características energéticas, apesar de tratar-se de uma empresa que oferece serviços.

Palavras chave: economia de energia; análise custo-benefício; cogeração; consultoria energética; refrigeração por absorção

I. INTRODUCTION

The need of using technology to increase energy efficiency in industrial processes and apply energy savings techniques to decrease production costs throughout the entire industry is currently a topic of great importance [1]. Reducing production costs improves the profitability of companies [2]; therefore, techniques for increasing efficiency and energy savings are not only employed or demanded by industries that produce goods [3], but also by companies that offer different types of services [4].

Applying energy savings strategies such as motion detectors, infra-red technology, operating time programs, energy-efficient lighting, fuel changes, burner changes, modernized auxiliary equipment, and renovated equipment, among others is fundamental to bring about significant savings, mainly in thermal and electrical energy bills. However, other alternatives can be studied and applied; for example, using different energy generation schemes by implementing power cycles and systems [5].

Companies aim at becoming more competitive in the international market with energy savings and increased energy efficiency, which create a demand for better quality products at lower costs on an increasing basis. Therefore, applying these engineering techniques, seek to obtain an economic and ecological benefit with high operational functionality that minimizes the risks for personnel.

Here, we present the results from a case study conducted in a warehouse with the aim of offering an energy solution or alternative [6]. To conduct this study, we measured, in the field and with specialized instruments, the energy consumption of the auxiliary process equipment, and checked the operation and performance of air-conditioning and lighting equipment. The objective was to understand the equipment operation and performance to quantify their impact on energy costs, and hence, create a proposal for increasing energy efficiency that would result in economic savings.

II. METHODOLOGY

The warehouse historical monthly energy consumption records were gathered from at least 12 months of bills issued by the Mexico's Federal Electricity Commission (Comisión Federal de Electricidad, CFE). This guaranteed that the data used in the analysis were real and objective. The data included the rate type, the connected load (CC, for its initials in Spanish), the contract demand (DC, for its initials in Spanish), the maximum demands, the billable demand (DF, for its initials in Spanish), the power factor (FP, for its initials in Spanish), the load factor (FC, for its initials in Spanish), the consumption per period, and in total, the average price of the energy consumed (Pm, for its initials in Spanish) and the discounts or penalties according to the power factor, among others (www.cfe.gob.mx), as well as the consumption of water and fuel.

Technical visits to each area and department of the warehouse were conducted to develop a detailed field survey. The survey included identifying all types of tubing (water, fuel, air-conditioning, etc.) and the type and quantity of lights, as well as gathering technical plate information from all the operating equipment and recording their physical operating parameters (e.g., temperature, pressure, capacity, flow, electrical parameters). Likewise, operators were visited to collect variables that could not be obtained directly from physical measurements, such as usage habits, maintenance hours, and considerations beyond maintenance controls, among others. This information was used to identify various opportunities for increasing efficiency and saving energy and improving operating programs and maintenance with the systems and equipment [7].

III. RESULTS

From the field surveys, we found that implementing a cogeneration system in the warehouse represents a savings opportunity [8,9]. This system would operate with a motor generator to produce electrical energy and an absorption cooling system to provide air-conditioning [10,11]. The current energy performance conditions of the entire warehouse are described below.

A. Current situation

The plant has a contract with CFE for a mediumvoltage rate (HM) with a supply of 13,200 V. It has two 350 kW generators, which generate electrical energy during peak hours and serve as backup equipment in case of outages. Table 1 shows the electrical energy consumption and maximum demands of the studied plant.

TABLE 1 ELECTRICITY CONSUMPTION AND DEMANDS 

Demand (kW) Consumption (kWh)
Month Base Intermediate Peak Billable Base Intermediate Peak Total
January 465 484 400 426 56,794 127,546 31,600 215,940
February 466 444 404 420 51,498 117,076 29,592 198,166
March 473 507 475 485 55,370 125,421 31,373 212,164
April 594 497 546 554 55,958 135,941 54,838 246,737
May 621 519 569 577 71,170 149,416 27,558 248,144
June 642 547 494 525 108,011 120,388 13,258 241,658
July 635 512 565 576 64,651 165,645 27,116 257,412
August 620 495 548 560 70,316 160,207 26,272 256,795
September 583 515 564 567 65,022 150,573 26,474 242,070
October 604 470 519 532 61,034 136,102 53,500 250,636
November 498 567 439 478 54,874 134,521 33,677 223,072
December 429 521 413 446 49,695 140,200 34,741 224,636
Minimum 429 444 400 420 49,695 117,076 13,258 198,166
Maximum 642 567 569 577 108,011 165,645 54,838 257,412
Average 553 506 495 512 63,699 138,586 32,500 234,786

The plant also has 14 package units of 25 tons of refrigeration (TR) each that supply air-conditioning to the entire warehouse; this is mainly used during summer when ambient temperatures increase. This equipment is activated in staggered phases throughout the day. The first four equipment packages are activated at 6:00 a.m., then, four more are activated at 12 p.m., and the six remaining are turned on at 2:00 p.m. Seven of them are turned off at 8:00 p.m., and the rest, at 11:00 p.m. (Fig. 1). This takes place during the eight-month season that is considered to have high ambient temperatures, which lasts from March to October. All the equipment operates for an average of 10.6 hours a day; however, the first four equipment units operate a total of 17 hours a day, experiencing greater wear, which reduces their lifespan compared to the rest of the equipment. Regarding the lights, the evaluation showed that they are in good condition and do not need changes or modifications.

FIG. 1 Staggered operation of the 14 equipment packages. 

The air-conditioning equipment is distributed throughout the entire area of the warehouse, offering adequate comfort. The operation of the first seven air conditioning units was measured in the field (Table 2 and Fig. 2); subsequently, this information was used for extrapolating energy consumption for the rest of the equipment packages. The first seven equipment packages that are turned on during the day are used 75% more than the others.

TABLE 2 TESTS AND FIELD MEASUREMENTS OF THE SEVEN EQUIPMENT PACKAGES 

FIG. 2 Load curve of the air-conditioning equipment for a full year. 

Table 3 reports the total consumption of the 14 equipment packages and their load percentage, in relation to the total consumption of the warehouse. Moreover, Table 4 shows that the consumption of the first seven equipment units that are turned on (the ones monitored in the field) represent approximately 80% of the energy consumption of all the air conditioning equipment.

TABLE 3 AIR-CONDITIONING ENERGY CONSUMPTION FOR THE 14 EQUIPMENT PACKAGES 

TABLE 4 AIR-CONDITIONING ENERGY CONSUMPTION FOR THE FIRST SEVEN EQUIPMENT PACKAGES TO BE TURNED ON 

The studied company uses natural gas, with an rates average calorific value of 36,421 kJ m-3 and a supply pressure of 2 kg cm-2. Natural gas is used at these in different areas of the warehouse (Table 5).

TABLE 5 FUEL CONSUMPTION 

B. Proposal

The proposal entails generating electrical energy with a motor generator powered by natural gas (Tables 6 and 7) and, at the same time, using the residual heat from gas exhaust and exhaust sleeves to produce air-conditioning with an absorption cooling system of lithium bromide-water (H2O-LiBr) as a working fluid, presenting a cooling capacity of 75 TR (commercial equipment).

TABLE 6 CHARACTERISTICS OF A COMMERCIAL MOTOR GENERATOR 

TABLE 7 INITIAL PARAMETERS FOR THE COGENERATION SYSTEM ANALYSIS 

The amount of available residual heat is 448 thermal kW. This power is reduced when considering the cooling coefficient performance (COP) of the absorption system (0.6 in this case), which will help substituting three equipment packages.

The system will require a new supply system of ice water to provide air-conditioning through a blower coil, which will substitute the three equipment packages of 25 TR each. To achieve this, it will be necessary to install ice water pumps, a condensing system, and a cooling tower. The three equipment packages to be substituted are three of the first four units that are turned on at 6:00 a.m. and turned off at 11:00 p.m. every day during the eight months that the warehouse uses air-conditioning.

By implementing this cogeneration system, an average monthly electrical energy savings of 234,786 kWh will be achieved with the additional benefit of 29,804 kWh in surplus energy per month, which could be exported at the DAC rate at the cost of 10% less than its billing price. In addition, an average monthly savings of 372 kW for billable demand would be obtained (Fig. 3). Concurrently, there will be a 155 m3 increase of ice water in the cooling tower per month with the installation of the absorption chiller. Table 8 shows the peripheral equipment consumption for each air-conditioning system along with the savings that would be gained thanks to the change in technology.

FIG. 3 Behavior of demands throughout the year. 

TABLE 8 COMPARISON OF AIR-CONDITIONING EQUIPMENT CONSUMPTION AND ENERGY SAVINGS 

The final evaluation considered the complete installation of the cogeneration system, which includes the motor generator, the ice water and condensed water pumping, the transfer tables, and the booths. Water from the powering system and replacement water will be used for evaporation in the cooling tower. A thorough civil engineering project is being contemplated to install the main and peripheral equipment, including the labor needed to position the tables, the generator equipment, and the air-conditioning equipment, and to remove the existing equipment. Also, adaptations and installations for supplying natural gas to the new generator equipment have been contemplated. Fig. 4 shows the conceptual arrangement of the proposed cogeneration system.

FIG. 4 General cogeneration system scheme. 

Regarding the energetic performance of the motor generator, it was observed that the total energy produced per year is higher than the energy that is currently consumed (Table 9). However, the demands (base, intermediate, and peak) of the warehouse (kWe) are higher than the installed capacity that has been proposed (Table 10). In this case, the lacking demand would be supplied by CFE.

TABLE 9 COGENERATION SYSTEM PERFORMANCE 

TABLE 10 ENERGY AND DEMAND ASSESSMENT Demand (kW) Energy produced (kWh) 

Note: The negative red numbers indicate energy surpluses.

The calculation of the new billable demand (DF, for its initials in Spanish) was obtained using expression (1):

where:

DP is the average maximum demand during the peak period

DI is the average maximum demand during the intermediate period

DB is the average maximum demand during the base period

DPI is the average maximum demand during the peak and intermediate periods

FRI and FRB are reduction factors with values of 0.150 and 0.300, respectively

Table 11 summarizes the warehouse potential consumption of natural gas, including the consumption of the proposed motor generator.

TABLE 11 NATURAL GAS CONSUMPTION IN THE WAREHOUSE 

C. Simple cost-benefit analysis

Based on the knowledge of current savings and consumption, a simple cost-benefit analysis was carried out for the period of the technical-financial proposal. To do this, it was necessary to identify the market prices of the different equipment and categories considered for this project (Table 12), including the cost of the equipment units and their complete installation. The latter entails interconnections, auxiliary equipment, adaptations, the civil engineering project, maneuvering, installation, and implementation. The average prices of consumables, the DAC rate, and the maintenance costs per kilowatt generated were also considered (Table 13).

TABLE 12 ANTICIPATED FINANCIAL INVESTMENT 

TABLE 13 COSTS CONSIDERED FOR THE FINANCIAL SAVINGS EVALUATION 

When assessing the consumption and savings according to the proposal, we considered the increase in water consumption (459 USD per month) and natural gas (11,350 USD per month). Furthermore, changing air-conditioning technology generates savings in energy consumption (27,508 kWh per month), which should be added to the surplus of electrical energy (29,804 kWh per month). The per item DF savings should be considered as the average monthly capacity of the motor generator (372 kW), with an average remaining billable demand deficit of 146 kW per month to be paid (Table 14).

TABLE 14 Cost-benefit analysis 

The investment payback period for this project is 2.9 years, which makes it an attractive project with outstanding advantages that benefit the company performance directly regardless of the CFE rates. Likewise, it guarantees the quality of energy inside the warehouse, thus promoting energy savings.

This project could cover 100% of the electrical energy that is consumed by the warehouse (207,278 kWh month-1), in addition to transporting 57,312 kWh per month at a rate of 10% below the DAC cost. Three air-conditioning equipment packages would be substituted by an absorption chiller, which consumes 54% less electrical energy.

IV. CONCLUSION

The proposed cogeneration system conformed of a motor generator and an absorption cooling equipment proved to be an adequate, viable, and technically feasible option for a warehouse. Moreover, the investment payback period for this project is very attractive, as the total cost of the project would be covered in less than three years, including maintenance costs. The cogeneration systems can be applied to both large or industrial companies that have significant levels of electrical and thermal energy consumption, and to small service-provider companies -as was demonstrated-, as long as they have the necessary primary inputs.

Nomenclature

CC Connected load (kW)

DF Billable demand (KW)

FP Power factor (%)

FC Load factor (%)

TR Tons of refrigeration

COP Coefficient of performance

T Temperature (°C)

GN Natural gas

GJ Giga Joules

DC Contract demand (kW)

CB Investment payback period (years)

DAC High domestic consumption rate ($ kWh-1)

CFE Comisión Federal de Electricidad

MCI Motor generador

kWe Electric kilowatt

kWt Thermal kilowatt

USD American dollar

REFERENCES

[1] S. M. Soler-Pérez, "Metodología general para la evaluación integral de la eficiencia energética en los centrales azucareros," Tecnología Química, vol. 31 (1), pp. 40-46, 2011. [ Links ]

[2] Conuee and Giz, "Manual para la Implementación de un Sistema de Gestión de la Energía," 2nd. Ed., Conuee /Giz , México, 2016. Available in: http://www.gob.mx/cms/uploads/attachment/file/119159/Manual_SGEn_Conuee_2da_Edicion.compressed.pdf. [ Links ]

[3] H. T. Ramírez, and G. A. Monforte, "Eficiencia de las estrategias de uso eficiente de energía eléctrica en hoteles de cinco estrellas en la ciudad de Mérida, Yucatán," in XI Congreso internacional de investigación en ciencias administrativas, 2007. [ Links ]

[4] Calidad y Sustentabilidad en la Edificación A.C., "Código de la conservación de la energía para las Edificaciones en México," CASESI, México, 2016. Available in: http://www.casedi.org.mx/quienes-somos/2-uncategorised. [ Links ]

[5] D. Staniaszek, and E. Lees, "Determining Energy Savings for Energy Efficiency Obligation Schemes," RAP, 2012. [ Links ]

[6] M. A. Lozano, and J. Ramos, "Análisis energético y económico de sistemas simples de cogeneración," Información Técnica, vol. 18(5), pp. 75-84, 2007. [ Links ]

[7] DOF, "Resolución por la que la comisión reguladora de energía expide la metodología para el cálculo de la eficiencia de los sistemas de cogeneración de energía eléctrica y los criterios para determinar la "Cogeneración Eficiente"," México, 2011. Available in: http://www.cre.gob.mx/documento/2299.pdf. [ Links ]

[8] M. F. Fernández, P. L. Huante, and C. A. Romo, "Sistemas de cogeneración," Boletín IIE, vol. 30 (2), pp. 67-72, 2006. [ Links ]

[9] E. V. Torres, P. M. Salazar, L. R. Lugo, and A. Torres, "Análisis exergoeconómico de una planta de cogeneración con turbina de gas considerando el proceso de formación del residuo", in CIBIM 10, Oporto, Portugal, 1387-1392, 2011. [ Links ]

[10] H. C. A. Orozco, "Ahorro de energía y eficiencia energética en sistemas de aire acondicionado y refrigeración," Scientia et Technica, vol. 10(24), pp. 127-132, 2004. [ Links ]

[11] F. Li, L. Duanmu, and X. L. Zhao, "Research and application of flue gas waste heat recovery in cogeneration based on absorption heat-exchange," Procedia Engineering, vol. 146, pp. 595-603, 2016. DOI: https://doi.org/10.1016/j.proeng.2016.06.407.Links ]

Cómo citar este artículo: I. Vera-Romero, "Generation of electric power and air conditioning by cogeneration: a proposal for energy saving," Revista Facultad de Ingenieria, vol. 27 (49), pp. 35-47, Sep. 2018

Received: June 08, 2018; Accepted: August 19, 2018

Creative Commons License This is an open-access article distributed under the terms of the Creative Commons Attribution License