<title-group>
<article-title xml:lang="es"><![CDATA[Ajuste protección de sobreexcitación ANSI 24 de un generador sincrónico para un relé Siemens 7UM62]]></article-title>
<article-title xml:lang="en"><![CDATA[Adjustment ANSI 24 overexcitation protection of a synchronous generator for a Siemens 7UM62 relay]]></article-title>
</title-group>
<contrib-group>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Caicedo Delgado]]></surname>
<given-names><![CDATA[Nayiver Gladys]]></given-names>
</name>
<xref ref-type="aff" rid="Aff"/>
</contrib>
<contrib contrib-type="author">
<name>
<surname><![CDATA[Andrade]]></surname>
<given-names><![CDATA[Carlos Alberto]]></given-names>
</name>
<xref ref-type="aff" rid="Aff"/>
</contrib>
</contrib-group>
<aff id="Af1">
<institution><![CDATA[,Universidad del Valle  ]]></institution>
<addr-line><![CDATA[Cali ]]></addr-line>
<country>Colombia</country>
</aff>
<aff id="Af2">
<institution><![CDATA[,Empresa Proing S.A  ]]></institution>
<addr-line><![CDATA[Cali ]]></addr-line>
<country>Colombia</country>
</aff>
<pub-date pub-type="pub">
<day>00</day>
<month>09</month>
<year>2019</year>
</pub-date>
<pub-date pub-type="epub">
<day>00</day>
<month>09</month>
<year>2019</year>
</pub-date>
<volume>23</volume>
<numero>61</numero>
<fpage>57</fpage>
<lpage>68</lpage>
<copyright-statement/>
<copyright-year/>
<self-uri xlink:href="http://www.scielo.org.co/scielo.php?script=sci_arttext&amp;pid=S0123-921X2019000300057&amp;lng=en&amp;nrm=iso"></self-uri><self-uri xlink:href="http://www.scielo.org.co/scielo.php?script=sci_abstract&amp;pid=S0123-921X2019000300057&amp;lng=en&amp;nrm=iso"></self-uri><self-uri xlink:href="http://www.scielo.org.co/scielo.php?script=sci_pdf&amp;pid=S0123-921X2019000300057&amp;lng=en&amp;nrm=iso"></self-uri><abstract abstract-type="short" xml:lang="es"><p><![CDATA[Resumen  Contexto:  Las funciones de protección de un grupo generador-transformador deben garantizar su vida útil cuando se presenta una condición de operación anormal, de esta manera se mejora la confiabilidad del servicio de energía eléctrica en el sistema eléctrico de potencia. Cuando la relación V/Hz del grupo se incrementa puede presentarse saturación en el núcleo magnético, induciendo un flujo de dispersión en los componentes no laminados que no están diseñados para conducirlo y puede ocurrir un daño en segundos; razón por la cual, estas máquinas se protegen con la función de protección (FDP) ANSI 24.  Metodología:  Este artículo presenta la teoría que justifica la implementación de la FDP ANSI 24 en un grupo generador-transformador y la metodología para calcular cada uno de sus parámetros de ajuste en un relé multifuncional Siemens 7UM62. La originalidad del artículo radica en que se explica su diagrama lógico de decisión de una manera clara y detallada, identificando las señales de entrada: ajustes, analógicas y binarias, y sus señales de salida. Este diagrama lógico se organizó en 3 subdiagramas para facilitar su comprensión e identificar las causas que originan sus salidas de alarmas, arranque, disparos o bloqueo.  Resultados:  Se obtuvo el diagrama de decisión detallado de la FDP ANSI 24, se describieron los criterios de ajuste de entrada de cada uno de los parámetros de ajustes y un procedimiento detallado para calcular cada uno. También, se obtuvieron los resultados numéricos de todos los ajustes para el grupo generador-transformador de la Unidad 1 de la Central Hidroeléctrica de Salvajina.  Conclusiones:  Se recomienda para una mayor precisión en los parámetros de ajuste obtener la característica de calentamiento V/Hz real o entregada por el fabricante de los equipos a proteger.]]></p></abstract>
<abstract abstract-type="short" xml:lang="en"><p><![CDATA[Abstract  Context:  The protection functions of a generator - transformer group must guarantee its useful life when an abnormal operating condition arises, thus improving the reliability of the electric power service in the electric power system. When the V/Hz ratio of the group increases, saturation may occur in the magnetic core and induce a dispersion flow in the non-laminated components that are not designed to conduct it, and damage can occur in seconds. This is the reason why machines are protected with the ANSI 24 protection function (FDP).  Methodology:  This article presents the theory that justifies the implementation of the ANSI 24 protection function in a generator-transformer group, as well as the methodology to calculate each of the adjustment parameters in a SIEMENS 7UM62 multifunctional relay. The article explains the logical decision diagram in a clear and detailed way, identifying the settings, input signals (analog and binary), and output signals. The logical diagram was organized in three subdiagrams to facilitate understanding and to identify the causes that originate its alarm, start, trip, or block outputs.  Results:  The detailed decision diagram of the ANSI 24 protection function was obtained; the input adjustment criteria of the adjustment parameters and a detailed procedure for calculating each were described. In addition, the numerical results of all the adjustments for the generator-transformer group of Unit 1 of the Salvajina hydroelectric power station were obtained.  Conclusions:  The results of this research recommend obtaining the actual V/Hz heating characteristic or confirming the one delivered by the manufacturer of the equipment to be protected, so that it is possible to have greater precision in the adjustment parameters.]]></p></abstract>
<kwd-group>
<kwd lng="es"><![CDATA[ANSI 24]]></kwd>
<kwd lng="es"><![CDATA[generador sincrónico]]></kwd>
<kwd lng="es"><![CDATA[protecciones eléctricas]]></kwd>
<kwd lng="en"><![CDATA[ANSI 24]]></kwd>
<kwd lng="en"><![CDATA[synchronous generator]]></kwd>
<kwd lng="en"><![CDATA[electrical protections]]></kwd>
</kwd-group>
</article-meta>
</front><back>
<ref-list>
<ref id="B1">
<nlm-citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Ceballos M.]]></surname>
<given-names><![CDATA[J.S.C]]></given-names>
</name>
</person-group>
<source><![CDATA[Criterios de ajuste para las protecciones de una unidad de generación de energía hidráulica en una PCH. Caso Amaime]]></source>
<year>2014</year>
<publisher-loc><![CDATA[Cali, Colombia ]]></publisher-loc>
<publisher-name><![CDATA[Programa de Ingeniería Eléctrica, Facultad de Ingeniería, Escuela de Ingeniería Eléctrica y Electrónica. Universidad del Valle]]></publisher-name>
</nlm-citation>
</ref>
<ref id="B2">
<nlm-citation citation-type="">
<collab>IEEE Guide for AC Generator Protection</collab>
<source><![CDATA[IEEE Std C37.102-2006 (Revison of IEEE Std C37.102-1995)]]></source>
<year>2006</year>
<page-range>1-177</page-range></nlm-citation>
</ref>
<ref id="B3">
<nlm-citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Muñoz]]></surname>
<given-names><![CDATA[J.C.]]></given-names>
</name>
<name>
<surname><![CDATA[Aragón]]></surname>
<given-names><![CDATA[L.E]]></given-names>
</name>
</person-group>
<source><![CDATA[Guía para la parametrización y pruebas de un relé numérico multifunción de protección de generador]]></source>
<year>2008</year>
<publisher-loc><![CDATA[Santiago de Cali, Colombia ]]></publisher-loc>
<publisher-name><![CDATA[Programa de Ingeniería Eléctrica, Facultad de Ingeniería, Departamento de Energética y Mecánica]]></publisher-name>
</nlm-citation>
</ref>
<ref id="B4">
<nlm-citation citation-type="book">
<person-group person-group-type="author">
<name>
<surname><![CDATA[Muñoz]]></surname>
<given-names><![CDATA[L.]]></given-names>
</name>
<name>
<surname><![CDATA[Caicedo]]></surname>
<given-names><![CDATA[G]]></given-names>
</name>
</person-group>
<source><![CDATA[Protección pérdida de campo de excitación de un generador sincrónico para un relé siemens 7UM62]]></source>
<year>2018</year>
<publisher-loc><![CDATA[Cali ]]></publisher-loc>
<publisher-name><![CDATA[Programa de Ingeniería Eléctrica, Facultad de Ingeniería, Escuela de Ingeniería Eléctrica y Electrónica. Universidad del Valle]]></publisher-name>
</nlm-citation>
</ref>
<ref id="B5">
<nlm-citation citation-type="">
<collab>Siemens</collab>
<source><![CDATA[SIPROTEC Multi-Functional Protective Relay 7UM62. Manual. V4.8;2013]]></source>
<year>2009</year>
</nlm-citation>
</ref>
</ref-list>
</back>
</article>